Rating | 60 deg C, 300 Vac, Horizontal flame. |
|
Conductor | 28 AWG - 15 AWG, stranded. |
|
Insulation | Extruded PVC, 20 mils min average. Only those colors listed on the Facing page may be employed. |
|
Assembly | Two to Nineteen Conductors. Different conductor sizes may be employed in one cord. |
|
Jacket | Extruded PVC, 31 mils min average, 23 mils minimum at any point. Only those colors listed on the Facing page may be employed. |
|
Standard | Appliance Wiring Material UL 758. |
|
Marking | General. |
|
Use | External interconnection or internal wiring of x-ray equipment where not exposed to abuse. |
|