Rating | 80 deg C, 30 Vac, Cable flame. |
|
Insulated Conductor | Labeled or complying with Manufacturer's AWM Procedure except that Styles rated 30 Vac for Class 2 operation may not be used. |
|
Assembly | Consists of two or more conductors, twisted pairs or groups of twisted conductors twisted together. The conductors or groups of conductors may be laid parallel forming a flat, oval or round cable. A barrier layer and/or fillers are optional. Manufacturer shall maintain a complete description of each assembly. May use same or mixed AWG size. |
|
Covering | Optional. A 6 mil or heavier Extruded PVC covering may be extruded over each twisted pair, groups of conductors, or the conductor assembly. |
|
Shield | Optional. |
|
Jacket | Extruded PVC; |
| Diameter of cable under jacket* | Minimum average thickness | Minimum thickness at any point |
| 0.425 inch or less | 30 mils | 24 mils |
| 0.426-0.700 inch | 45 mils | 36 mils |
| 0.701-1.000 inch | 60 mils | 48 mils |
| 1.001-1.500 inch | 80 mils | 64 mils |
| 1.501-2.500 inch | 110 mils | 88 mils |
| 2.501 inch and larger | 140 mils | 112 mils |
| * - Major diameter if cable is flat or oval. |
|
Braid | Optional. |
|
Standard | Appliance Wiring Material UL 758. |
|
Marking | General. |
|
Use | Internal wiring or external wiring. |
|