Rating | 105 deg C, 300 Vac, FT2 flame. |
|
Conductor | 26 AWG - 14 AWG stranded. Different conductor sizes may be employed in one cord. |
|
Insulation | Extruded PVC, 30 mils min average thickness, 27 mils minimum thickness at any point. Color coding of insulation not required. |
|
Assembly | Two to six conductors, same as type SJT. |
|
Jacket | Extruded PVC, 30 mils min average thickness, 24 mils minimum thickness at any point. |
|
Standard | Appliance Wiring Material UL 758. |
|
Marking | General. |
|
Use | Internal Wiring of Electronic Equipment or Appliances. |
|