Rating | 80 deg C, Voltage Not Specified, Horizontal flame. |
|
Conductor | 30 AWG - 16 AWG, solid or stranded. |
|
Insulation | Extruded SRPVC, 9 mils minimum average thickness, 7 mils minimum thickness at any point. |
|
Assembly | Two or three conductors laid parallel, twisted, or cabled together, length of lay is not specified. Barrier layer and/or fillers optional. |
|
Shield | Optional. |
|
Jacket | Extruded PVC, 12 mils minimum average thickness, 10 mils minimum thickness at any point. |
|
Shield | Optional. |
|
Jacket | Optional. Extruded PVC, 12 mils minimum average thickness, 10 mils minimum thickness at any point. |
|
Standard | Appliance Wiring Material UL 758. |
|
Marking | General. |
|
Use | Internal wiring where not exposed to movement or mechanical abuse. |
|