| Rating | 60 deg C, 300 Vac, Horizontal flame. |
|
| Conductor | No. 28 AWG - 16 AWG solid or stranded. |
|
| Insulation | Extruded PVC, 15 mils min average, 13 mils minimum at any point. |
|
| Assembly | Two to sixty-one conductors. Two conductors may be laid parallel or twisted together. Three or more conductors shall be twisted together. Lay of insulated conductors not specified, but with a twist opposite in direction to the direction in which the helical cord is wound. |
|
| Shield | Optional. Over one or more of the individually insulated conductors may be shielded or groups of individually insulated conductors may be shielded. Shielding over conductor shall consist of 36-30 AWG applied as a wrap or braid. |
|
| Jacket | Extruded PVC |
| dia in inches |
| 0.425 or less | 32 mils min average | 26 mils minimum at any point |
| 0.426-0.700 dia | 60 avg | 48 min |
| 0.701-1.500 dia | 80 avg | 64 min |
|
| Standard | Appliance Wiring Material UL 758. |
|
| Marking | General. |
|
| Use | Internal wiring. |
|