			| Rating | 105 deg C, 600 or 1000 Vac, Cable flame. | 
			|  | 
			| Conductor | 40 AWG minimum. | 
			|  | 
			| Insulated Conductor | Labeled or complying with manufacturer's AWM Procedure. | 
			|  | 
			| Assembly | Two or more conductors or groups of conductors laid parallel or twisted forming a flat, oval or round cable. The lay of the conductors is not specified. A barrier layer and/or fillers are optional. May use same or mixed AWG size. | 
			|  | 
			| Covering | Optional, Extruded PVC, 6 mils minimum thickness at any point. | 
			|  | 
			| Shield | Optional. | 
			|  | 
			| Jacket | Extruded PVC. | 
			|  | Diameter of cable under jacket* | Minimum average thickness | Minimum thickness at any point | 
			|  | 0.700 inch or less | 30 mils | 24 mils | 
			|  | 0.701-1.000 inch | 60 mils | 48 mils | 
			|  | 1.001-1.501 inch | 80 mils | 64 mils | 
			|  | 1.501-2.500 inch | 110 mils | 88 mils | 
			|  | * - Major diameter if cable is flat or oval | 
			|  | 
			| Standard | Appliance Wiring Material UL 758. | 
			|  | 
			| Marking | General. | 
			|  | 
			| Use | External interconnection or internal wiring. | 
			|  |