APPLIANCE WIRING MATERIAL
Subj.758 Section 2 Page 2604 Issued:1973-01-03
Revised:2012-04-20
Style 2604 Multiple-conductor cable using non-integral jacket

Rating75 deg C, 90 Vac, Horizontal flame.
Conductor32 AWG - 20 AWG stranded tinned, coated, or bare, flat or round copper
InsulationPE, 7 mils min average, 6 mils min. at any point, or Labled or complying with Section 2 of the Manufacturer's AWM Procedure, having a minimum rating of 75 deg C, 90 Volts.
AssemblyOne or three conductors or flat cables. Insulation width on outside edges, 6 mils min. Minimum spacing between conductors 5 mils. Maximum 0.375 inch thickness over jacket. Maximum 3-0.5 inch width on outside of jacket.
ShieldOptional, or expanded metallic ground planes, one or both sides. The ground plane may be flat copper or aluminum and may be employed as a solid or mesh constructions.
BraidOptional.
JacketPVC, 60 mils min average, 48 mils minimum at any point.
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseExternal interconnection of electronic equipment.