APPLIANCE WIRING MATERIAL
Subj.758 Section 2 Page 2652 Issued:1973-09-05
Revised:2012-02-24
Style 2652 Multiple-conductor cable using non-integral jacket.

Rating60 deg C, 300 Vac, FT2 flame.
Conductor18 AWG - 10 AWG, stranded.
InsulationExtruded PVC, 30 mils minimum average thickness, 27 mils minimum thickness at any point.
AssemblyFour conductors, same as Type SJT Cord.
JacketExtruded PVC, 30 mils minimum average thickness, 24 mils minimum thickness at any point.
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseInterconnecting Cord.