APPLIANCE WIRING MATERIAL
Subj.758 Section 2 Page 2735 Issued:1975-05-12
Revised:2011-08-04
Style 2735 Multiple-Conductor Parallel Cable with Extruded Non-Integral Jacket

Rating60 deg C, 30 Vac, Horizontal flame.
InsulationLabeled Style 2445
ShieldOptional, or expanded metallic ground planes, one or both sides. The ground plane may be flat copper or aluminum and may be employed as a solid or mesh constructions.
JacketExtruded PVC
Diameter of core assembly under jacket (inches)Minimum average thickness (mils)Minimum thickness at any point (mils)
2.250 or less3024
2.251-4.0004536
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseExternal interconnection of electronic equipment, in Class 2 or Class 3 circuits where protected from mechanical abuse.

UL and the UL Logo are trademarks of UL LLC © 2024