APPLIANCE WIRING MATERIAL
Subj.758 Section 2 Page 2789 Issued:1976-05-21
Revised:2013-03-04
Style 2789 Multiple Conductor Cable with Extruded Non-integral Jacket

Rating60 deg C, 30 Vac, Cable flame.
Insulated ConductorLabeled or complies with this Manufacturers AWM singles Procedure.
AssemblyTwo or more insulated singles or groups of insulated singles cabled together to form a flat, oval or round assembly. Barrier layer and/or fillers optional. May use same or mixed AWG size. Manufacturer shall maintain a complete description of each assembly.
CoveringOptional, extruded PVC, 5 mils minimum thickness at any point, over the conductor assembly or extruded PTFE, PFA, FEP or ETFE, 8 mils minimum average thickness, 6 mils minimum thickness at any point.
ShieldOptional.
CoveringOptional, extruded PVC, 5 mils minimum thickness at any point, over the conductor assembly or extruded PTFE, PFA, FEP or ETFE, 8 mils minimum average thickness, 6 mils minimum thickness at any point.
ShieldOptional.
JacketExtruded PVC.
Major diameter of assembly under jacket*Minimum average thicknessMinimum thickness at any point
0.700 inch or less30 mils24 mils
0.701-1.000 inch45 mils36 mils
1.001-1.500 inch60 mils48 mils
1.501-2.500 inch80 mils64 mils
2.501-4.000 inch110 mils88 mils
4.001 inch or larger140 mil112 mils
* - Major diameter if cable is flat or oval.
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseInternal Wiring and External Interconnection in Class 2 Circuits of Electronic Equipment.