Rating | 105 deg C, 600 Vac, Oil Resistant 60 or 80C, Moisture Resistant 75C Gasoline Resistant 30 deg C. |
|
Conductor | 26 AWG - 12 AWG solid or stranded round, tinned or bare copper. |
|
Insulation | PVC, 15 mils min average, 13 mils minimum at any point. |
|
Assembly | Two or more conductors, twisted pairs or groups of twisted conductors twisted together. the conductors or groups of conductors may be laid parallel forming a flat, oval or round cable. The lay of the conductors is not specified. A barrier layer and/or fillers are optional. Manufacturershall maintain a complete description of each assembly. May use same or mixed AWG size. |
|
Shield | Optional. |
|
Covering | Extruded nylon in 4 mil min thickness at any point, major dia. of cable in inches of 0.460 or less, 5 mils min thickness at any point; 0.451-0.550, 6 mils; 0.551-0.750, 7 mils; 0.751-0.950, 8 mils; 0.951-1.200, 9 mils. (refer to the latest bulletin under Subject 83 for "Gasoline-Resistant Nylon Jacketing Compounds"). |
|
Jacket | PVC |
| major dia in inches |
| 0.350 or less | 25 mils min average | 20 mils minimum at any point |
| 0.351-0.450 dia | 30 avg | 24 min |
| 0.451-0.550 dia | 40 avg | 32 min |
| 0.551-0.750 dia | 50 avg | 40 min |
| 0.751-0.950 dia | 60 avg | 48 min |
| 0.951-1.200 dia | 70 avg | 56 min |
|
Standard | Appliance Wiring Material UL 758. |
|
Marking | General. |
|
Use | External interconnection of electronic equipment where exposed to temperatures not exceeding 105 deg C in dry locations, 30 deg C in liquid gasoline, 75 deg C in gasoline vapor, 75 deg C in wet location, 60 deg C or 80 deg C (whichever is applicable) in oil and where the acceptability of the combination is to be determined by Underwriters Laboratories Inc. |
|