APPLIANCE WIRING MATERIAL
Subj.758 Section 2 Page 2889 Issued:1977-09-30
Revised:2019-11-07
Style 2889 Multiple-conductor cable using non-integral jacket

Rating90 deg C, 600 Vac, Cable flame, Moisture Resistant 60 deg C.
InsulationLabeled or complying with Manufacturer's AWM Procedure.
AssemblyTwo or more conductors, twisted pairs or groups of twisted conductors twisted together. The conductors or groups of conductors may be laid parallel forming a flat, oval or round cable. The lay of the conductors is not specified. A barrier layer and/or fillers are optional. Manufacturer shall maintain a complete description of each assembly. May use same or mixed AWG size.
ShieldOptional.
CoveringOptional. A 6 mil or heavier PVC covering may be extruded over the conductor assembly.
JacketPVC
major dia in inches
0.700 or less30 mils min average24 mils minimum at any point
0.701-1.000 dia60 avg48 min
1.001-1.500 dia80 avg64 min
1.501-2.500 dia110 avg88 min
2.501 dia or larger140 avg112 min
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseInternal wiring of electric signs outdoors, non-weatherproof.