APPLIANCE WIRING MATERIAL
Subj.758 Section 2 Page 2905 Issued:1978-01-30
Revised:2019-11-07
Style 2905 Multiple-conductor cable using non-integral jacket.

Rating80 deg C, Voltage not specified, Horizontal flame.
Conductor40 AWG min.
InsulationLabeled or complying with manufacturer's AWM procedure.
AssemblyConsists of two or more conductors, twisted pairs or groups of twisted conductors twisted together. the conductors or groups of conductors may be laid parallel forming a flat, oval or round cable. The lay of the conductors is not specified. A barrier layer and/or fillers are optional. Manufacturer shall maintain a complete description of each assembly. May use same or mixed AWG size.
ShieldOptional.
CoveringOptional. A 6 mil or heavier Extruded PVC covering may be over the conductor assembly.
JacketExtruded PVC;
major dia in inches
0.350 or less15 mils minimum average thickness12 mils minimum thickness at any point
0.351-0.700 dia30 avg24 min
0.701-1.000 dia45 avg36 min
1.001-1.500 dia60 avg48 min.
- Major dia if cable is flat or oval.
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseInternal wiring. Tags may indicate the following: "600 volts Peak for Electronic use only".

UL and the UL Logo are trademarks of UL LLC © 2024