APPLIANCE WIRING MATERIAL
Subj.758 Section 2 Page 2922 Issued:1978-05-10
Revised:2012-04-23
Style 2922 Multiple-conductor cable with extruded non-integral jacket.

Rating90 deg C, Voltage not specified, Horizontal flame.
InsulationLabeled or complying with manufacturer's AWM procedure.
AssemblyTwo or more twisted insulated singles or groups of twisted singles twisted together. Lay not specified. Barrier layer and/or fillers optional. Manufacturer shall maintain a complete description of each assembly.
ShieldOptional.
JacketExtruded ETFE.
Diameter of core assembly under jacketMinimum average thicknessMinimum thickness at any point
0.425 inch or less13 mils10 mils
0.426-0.700 inch20 mils18 mils
0.701-1.500 inch30 mils24 mils
1.501-2.500 inch45 mils36 mils
2.501 inch or larger60 mils48 mils
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseInternal wiring.