| Rating | 80 deg C, 150 Vac, Cable flame. |
|
| Insulated Conductor | Labeled or complying with Manufacturer's AWM Procedure having a minimum rating of 80 deg C, 150 Vac.
|
|
| Assembly | Consists of two or more conductors, twisted pairs or groups of twisted conductors twisted together. The conductors or groups of conductors may be laid parallel forming a flat, oval or round cable. The lay of the conductors is not specified. A barrier layer and/or fillers are optional. Manufacturer shall maintain a complete description of each assembly. May use same or mixed AWG size.
|
|
| Covering | Optional. A 6 mils or heavier PVC covering may be extruded over the conductor assembly. |
|
| Shield | Optional. |
|
| Jacket | Extruded PVC |
| Diameter of cable under jacket in inches | Minimum average thickness | Minimum thickness at any point |
| 0.700 or less | 45 mils | 36 mils |
| 0.701-1.500 | 60 mils | 48 mils |
| 1.501-2.500 | 80 mils | 64 mils |
| 2.501 and larger | 110 mils | 88 mils |
|
| Standard | Appliance Wiring Material UL 758. |
|
| Marking | General. |
|
| Use | Internal wiring or external interconnection of electronic equipment. |
|