Rating | 105 deg C, 30 Vac, Cable flame. |
|
Insulated Conductor | 40 AWG minimum. Labeled or complying with Manufacturer's AWM Procedure having a minimum rating of 105°C.
|
|
Assembly | Consists of two or more conductors, twisted pairs or groups of twisted conductors twisted together. The conductors or groups of conductors may be laid parallel forming a flat, oval or round cable. The lay of the conductors is not specified. A barrier layer and/or fillers are optional. Manufacturer shall maintain a complete description of each assembly. May use same or mixed AWG size. |
|
Covering | Optional. A 6 mils or heavier PVC covering may be extruded over the conductor assembly. |
|
Shield | Optional. |
|
Jacket | Extruded PVC |
| Diameter of core assembly under jacket | Minimum average thickness | Minimum thickness at any point |
| 0.425 inch or less | 35 mils | 28 mils |
| 0.426-0.700 inch | 45 mils | 36 mils |
| 0.701-1.000 inch | 60 mils | 48 mils |
| 1.001-1.500 inch | 80 mils | 64 mils |
|
Standard | Appliance Wiring Material UL 758. |
|
Marking | General. |
|
Use | External interconnection of electronic equipment, Class 2 Circuits only. |
|