Rating | 60 deg C, 30 Vac, Horizontal flame. |
|
Insulated Conductor | 40 AWG minimum. Labeled or complying with manufacturer's AWM procedure. |
|
Assembly | Two or more conductors, twisted pairs or groups of twisted conductors twisted together. The conductors or groups of conductors may be laid parallel forming a flat, oval or round cable. The lay of the conductors is not specified. A barrier layer and/or fillers are optional. Manufacturer shall maintain a complete description of each assembly. May use same or mixed AWG size. |
|
Covering | Optional, extruded PVC, 6 mils minimum thickness at any point, over the conductor assembly. |
|
Shield | Optional. |
|
Jacket | Extruded PVC. |
| Diameter under jacket | Minimum average thickness | Minimum thickness at any point |
| 0.250 inch or less | 15 mils | 12 mils |
| 0.251-0.425 inch | 30 mils | 24 mils |
| 0.426-0.700 inch | 45 mils | 36 mils |
| 0.701-1.000 inch | 60 mils | 48 mils |
| 1.001-1.500 inch | 80 mils | 64 mils |
| 1.501-2.500 inch | 110 mils | 88 mils |
| 2.501 inch and larger | 140 mils | 112 mils |
| - Major diameter if cable is flat or oval. |
|
Standard | Appliance Wiring Material UL 758. |
|
Marking | General. |
|
Use | Internal wiring with Class 2 Circuits only. |
|