APPLIANCE WIRING MATERIAL
Subj.758 Section 3 Page 3005 Issued:1959-05-01
Revised:2011-10-14
Style 3005 Insulated Wire.

Rating75 deg C, 600 Vac, FT2 flame.
Conductor14 AWG - 12 AWG, solid or stranded, bare or tinned copper, separators and splices per the requirements in Standard UL 44.
InsulationCP, CPE, EP, EPCV, SBR/NR, Silicone or XLPE, nominal 1/32 inch (not a requirement), 30 mils minimum average, 27 mils minimum at any point.
CoveringBraid. A wrap may be used in lieu of a braid and shall comply with the requirements in Standard UL 44. Covering may also be dry or saturated.
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseIn appliances in dry locations where exposed to temperatures not exceeding 75 deg C.