Rating | 105 deg C,1000 Vac, Horizontal Flame. |
|
Conductor | 18 AWG - 400 MCM, solid or stranded. |
|
Insulation | Extruded XLPO |
| AWG Size | mm/mils min. avg. | mm/mils min. at any point |
| 18-6 | 0.70/28 | 0.63/25 |
| 4-2 | 0.90/35 | 0.81/32 |
| 1 | 1.00/39 | 0.90/35 |
| 2/0-3/0 | 1.10/43 | 1.00/39 |
| 4/0 | 1.20/47 | 1.08/42 |
| 250 MCM | 1.40/55 | 1.26/50 |
| 300 MCM | 1.60/63 | 1.44/57 |
| 400 MCM | 1.80/71 | 1.62/64 |
|
Standard | Appliance Wiring Material UL 758. |
|
Marking | General. |
|
Use | Internal Wiring where not subjected to movement or mechanical abuse, or where totally enclosed. |
|