Rating | 75 deg C, 600 Vac, FT2 flame. |
|
Conductor | 14 AWG - 12 AWG, solid or stranded copper, tinning, separators and splices same as required for Type RH per UL 44. |
|
Insulation | Extruded CP, extruded CPE, extruded EP, extruded EPCV, extruded SBR/NR, extruded Silicone or extruded XLPE, 45 mils min average, 40 mils minimum at any point. |
|
Covering | Braid. A wrap may be used in lieu of a braid and shall comply with the requirements in UL 44. Covering may also be dry or saturated. |
|
Standard | Appliance Wiring Material UL 758. |
|
Marking | General. |
|
Use | Internal wiring of appliances in dry locations where exposed to temperatures not exceeding 75 deg C. |
|