APPLIANCE WIRING MATERIAL
Subj.758 Section 3 Page 30093 Issued:2021-03-23
Revised:2021-03-25
Style 30093 Single conductor with extruded insulation.

Rating105 deg C, 600 Vac, Horizontal flame.
Conductor14 AWG - 1000 kcmil, solid or stranded.
InsulationExtruded EPDM
Conductor sizeMinimum average thicknessMinimum thickness at any point
14~10AWG45mils41mils
8~2 AWG60 mils54 mils
1/0~4/0 AWG80 mils72 mils
250~500 kcmil95 mils86 mils
500~1000 kcmil110 mils99 mils
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseInternal Wiring.