APPLIANCE WIRING MATERIAL
Subj.758 Section 3 Page 3014 Issued:1959-05-01
Revised:2012-03-12
Style 3014 Single Conductor with Extruded Insulation and Non-Extruded Covering

Rating75 deg C, 600 Vac, FT2 flame.
Conductor1 AWG - 4/0 AWG, solid or stranded copper, tinning, separators and splices same as required for Type RH per UL 44.
InsulationExtruded CP, CPE, EP, EPCV, SBR/NR, Silicone or XLPE, 80 mils minimum average thickness, 72 mils minimum thickness at any point.
CoveringTwo fibrous coverings required, same as for Type RH Wire.
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseIn appliances in dry locations where exposed to temperatures not exceeding 75 deg C.

UL and the UL Logo are trademarks of UL LLC © 2024