APPLIANCE WIRING MATERIAL
Subj.758 Section 3 Page 3055 Issued:1959-05-01
Revised:2012-07-13
Style 3055 Single Conductor with Extruded Insulation with a Non-extruded Non-integral Jacket.

Rating60 deg C, 600 Vac, Horizontal flame.
Conductor8 AWG - 2 AWG solid or stranded round.
InsulationExtruded SRB/NR, 60 mils min average, 54 mils minimum at any point.
CoveringTwo required. Closely woven cotton braid, dry, lacquered, varnished, waxed or asphalt treated or glass fiber braid, lacquered.
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseFor use as Motor Leads, or For Use as Plug Board Leads on Electric Accounting, Bookkeeping or Time Recording Equipment.