APPLIANCE WIRING MATERIAL
Subj.758 Section 3 Page 3090 Issued:1959-05-01
Revised:2012-04-04
Style 3090 Single conductor with extruded insulation

Rating75 deg C, 1000 Vac, Horizontal Flame.
Conductor12 AWG - 9 AWG, solid or stranded.
InsulationExtruded SRB/NR, 45 mils minimum average thickness, 40 mils minimum thickness at any point.
CoveringFibrous braid. A wrap may be used in lieu of a braid and shall comply with the requirements outlined in the Standard for Rubber-Covered Wires and Cables. Covering may also be saturated.
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseIn appliances in dry locations.