APPLIANCE WIRING MATERIAL
Subj.758 Section 3 Page 3114 Issued:1959-05-01
Revised:2011-10-18
Style 3114 Single conductor with extruded insulation.

Rating150 deg C, 600 Vac, Horizontal flame.
ConductorMinimum 0.0015 inch diameter Resistance Wire spirally applied around a glass-fiber core with a minimum of 20 turns per inch.
InsulationExtruded SR, 60 mils minimum average thickness, 54 mils minimum thickness at any point.
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseInternal wiring where protected from mechanical injury.

UL and the UL Logo are trademarks of UL LLC © 2024