Rating | 125 deg C, 600 Vac, 750 Vdc, Horizontal flame. |
|
Semi-Conductive Layer | Optional, extruded or non-extruded semi-conductive polymeric layer may be provided over the conductor. |
|
Conductor | 30 AWG - 2000 kcmil, solid or stranded. |
|
Insulation | Extruded XLPE. |
| Conductor size | Minimum average thickness | Minimum thickness at any point |
| 30-9 AWG | 30 mils | 27 mils |
| 8-2 AWG | 45 mils | 40 mils |
| 1-4/0 AWG | 55 mils | 50 mils |
| 213-500 kcmil | 65 mils | 58 mils |
| 501-1000 kcmil | 80 mils | 72 mils |
| 1001-2000 kcmil | 95 mils | 86 mils |
|
Standard | Appliance Wiring Material UL 758. |
|
Marking | General. |
|
Use | For use as Motor Leads or Internal Wiring of appliances. Tags may indicate the following: 2500 volt peak - For Electronic Use Only. |
|