APPLIANCE WIRING MATERIAL
Subj.758 Section 3 Page 3292 Issued:1975-02-07
Revised:2012-01-29
Style 3292 Single or multiple conductor with extruded insulation

Rating105 deg C, 600 Vac, Horizontal flame, Oil Resistant 80 deg C (optional).
ConductorNos. 30 - 4/0 AWG, solid or stranded, tinned, bare or silver plated copper or solid or stranded coated high strength copper - min 90% conductivity.
InsulationIrradiated Polyhalocarbon
30-9 AWG conductor size30 mils min average27 mils minimum at any point
9 AWG45 avg41 min
7-2 AWG60 avg54 min
1-4/0 AWG78 avg70 min
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseFor use as Motor Leads or Internal Wiring of Appliances. Tags may indicate the following: 1) 2500 V Peak - For Electronic Use Only 2) Suitable for Immersion in Oil at 80 deg C

UL and the UL Logo are trademarks of UL LLC © 2024