APPLIANCE WIRING MATERIAL
Subj.758 Section 3 Page 3307 Issued:1976-06-22
Revised:2011-11-21
Style 3307 Single conductor with exturded insulation

Rating200 deg C, 600 Vac, Horizontal flame.
Conductor1 AWG - 500 kcmil strands over 0.015 in stranded, tinned or plated copper, or nickel.
InsulationSR - SILICONE
1-4/0 AWG conductor size80 mils min average72 mils minimum at any point
250-500 MCM95 avg86min
See facing page for compound designation.
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseInternal wiring of appliances.

UL and the UL Logo are trademarks of UL LLC © 2024