Rating | 125 deg C, 600 Vac, 750 Vdc. No flexing - 150 deg C, 600 Vac or 750 Vdc. Horizontal flame. |
|
Conductor | 26 AWG - 500 kcmil, solid or stranded. |
|
Insulation | Extruded EPDM. |
| Conductor size | Minimum average thickness | Minimum thickness at any point |
| 26-9 AWG | 45 mils | 41 mils |
| 8-2 AWG | 60 mils | 54 mils |
| 1-4/0 AWG | 80 mils | 72 mils |
| 250-500 kcmil | 95 mils | 86 mils |
|
Standard | Appliance Wiring Material UL 758. |
|
Marking | General. |
|
Use | Motor Leads and Internal Wiring of Appliances where exposed to temperatures not exceeding 125 deg C. Where no flexing occurs either after installation of during servicing, temperatures not to exceed 150 deg C. |
|