Rating | 150 or 200 deg C, 600 Vac, Horizontal flame. |
|
Conductor | 26 AWG - 750 kcmil solid or stranded. Copper shall be tin, nickel or silver coated. If tinned copper strands are used, they shall be 0.0152 inch in diameter or larger. |
|
Insulation | Extruded SR |
| Conductor size | Minimum average thickness | Minimum thickness at any point |
| 26-10 AWG | 45 mils | 40 mils |
| 8-2 AWG | 60 mils 54 mils |
| 1-4/0 AWG | 80 mils | 72 mils |
| 250-500 kcmil | 95 mils | 85 mils |
| 501-750 kcmil | 110 mils | 99 mils |
|
Covering | Silicone, nylon or acrylic based emulsion finished polyaramid braid. |
|
Standard | Appliance Wiring Material UL 758. |
|
Marking | General. |
|
Use | Internal Wiring of Appliances or leads for hazardous location motors. |
|