Rating | 105 deg C, 600 Vac, FT2 flame. |
|
Conductor | 16 AWG - 1000 kcmil, stranded, tinned or bare copper. The conductor stranding shall be as follows: |
| Conductor size | Minimum number of strands |
| 16-2 AWG | 7 |
| 1-4/0 AWG | 19 |
| 250-500 kcmil | 37 |
| 550-1000 kcmil | 61 |
|
Insulation | Extruded XLPE. |
| Conductor size | Minimum average thickness | Minimum thickness at any point |
| 16-9 AWG | 30 mils | 27 mils |
| 8-2 AWG | 45 mils | 40 mils |
| 1-4/0 AWG | 55 mils | 50 mils |
| 250-500 kcmil | 65 mils | 58 mils |
| 600-1000 kcmil | 80 mils | 72 mils |
|
Standard | Appliance Wiring Material UL 758. |
|
Marking | General. |
|
Use | Conductors in Single-and Multiple-Conductor Shipboard Cable, Marine. |
|