Rating | 100 deg C, 600 Vac, Horizontal flame. |
|
Conductor | 16 AWG - 1000kcmil, conventional or compressed concentric-lay stranded. The conductor stranding shall be as follows: |
| Conductor sizes | Number of strands (Min) |
| 16-2 AWG | 7 |
| 1-4/0 AWG | 19 |
| 250-500 kcmil | 37 |
| 550-1000 kcmil | 61 |
|
Insulation | Extruded XLPO. |
| Conductor size | Min Average thickness (mil) | Min Thickness at any point (mils) |
| 16-9 AWG | 30 | 27 |
| 8-2 AWG | 45 | 40 |
| 1-4/0 AWG | 55 | 50 |
| 250-450 kcmil | 65 | 58 |
| 500-1000 kcmil | 80 | 72 |
|
Standard | Appliance Wiring Material UL 758. |
|
Marking | General. |
|
Use | Conductors in Single-and Multiple-Conductor Shipboard Cable, Marine. |
|