APPLIANCE WIRING MATERIAL
Subj.758 Section 3 Page 3513 Issued:1987-08-18
Revised:2015-10-13
Style 3513 Single Conductor with Extruded Insulation

Rating200 deg C, 600 Vac, Horizontal Flame.
Conductor0.5 - 250 sq mm, solid or stranded copper (tin, nickel or silver coated). If tinned copper strands are used, they shall be 0.0152 in diameter or larger.
SeparatorOptional.
InsulationExtruded Silicone Rubber.
Conductor SizeMinimum AverageMinimum at any point
0.5-4.0 sq mm30 mils27 mils
4.1-9.0 sq mm45 mils40 mils
9.1-35.0 sq mm60 mils54 mils
35.1-100.0 sq mm80 mils72 mils
100.1-250.0 sq mm95 mils85 mils
CoveringSame as for Type SF Fixture Wire.
BraidOptional.
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseInternal Wiring.

UL and the UL Logo are trademarks of UL LLC © 2024