Rating | 150 deg C, 600 Vac, Horizontal flame. |
|
Conductor | 18 AWG - 4 AWG solid or stranded, coated. May employ rope lay construction. |
|
Insulation | Extruded SR - Silicone Rubber |
| AWG Conductor Size | Minimum average thickness (mils) | Minimum thickness at any point (mils) |
| 18-9 | 45 | 40 |
| 8-4 | 60 | 55 |
|
Standard | Appliance Wiring Material UL 758. |
|
Marking | General. |
|
Use | Internal wiring of appliances where not subjected to flexing or motion. |
|