Rating | 200 deg C for Insulation, 90 deg C for Covering, 600 Vac, Horizontal flame. |
|
Conductor | 18 AWG - 750 kcmil, solid or stranded. |
|
Insulation | Extruded SR. |
| Conductor size | Minimum average thickness | Minimum thickness at any point |
| 18 - 12 AWG | 30 mils | 27 mils |
| 10 AWG | 45 mils | 40 mils |
| 8-2 AWG | 60 mils | 54 mils |
| 1-4/0 AWG | 80 mils | 72 mils |
| 250-750 kcmil | 95 mils | 85 mils |
|
Braid | |
| Conductor size | Minimum average thickness |
| 18-2 AWG | 7.5 mils |
| 1-3/0 AWG | 20 mils |
| 4/0 AWG - 750 kcmil | 30 mils |
|
Covering | Extruded Nylon. |
| Conductor size | Minimum thickness at any point |
| 18-10 AWG | 4 mils |
| 8-6 AWG | 7 mils | 4-500 kcmil | 8 mils |
| 550-750 kcmil | 9 mils |
|
Standard | Appliance Wiring Material UL 758. |
|
Marking | General. |
|
Use | Internal wiring of appliances. |
|