APPLIANCE WIRING MATERIAL
Subj.758 Section 3 Page 3614 Issued:1998-01-27
Revised:2012-07-19
Style 3614 Single Conductor with Extruded Insulation.

Rating125 deg C, No flexing for 150 deg C, 1000 Vac, Horizontal flame.
Conductor26 AWG - 500 kcmil, solid or stranded.
InsulationExtruded EPDM, See facing page for compound designation.
Conductor sizeMinimum averageMinimum at any point
26-9 AWG45 mils41 mils
8-2 AWG60 mils54 mils
1-4/0 AWG80 mils72 mils
250-500 kcmil95 mils86 mils
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseInternal wiring, where no flexing occurs either after installation or during servicing.

UL and the UL Logo are trademarks of UL LLC © 2024