APPLIANCE WIRING MATERIAL
Subj.758 Section 3 Page 3809 Issued:2007-07-18
Revised:2011-10-25
Style 3809 Single conductor with extruded insulation.

Rating90 deg C, 600 V ac, Horizontal Flame. 60C Oil Resistant.
Conductor24 AWG - 500 kcmil, solid or stranded.
InsulationExtruded XLPE, 12 mils minimum average thickness, 11 mils minimum thickness at any point.
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseInternal wiring where not subjected to movement or mechanical damage.