Rating | 105 deg C, 1500 V, Horizontal flame. |
|
Conductor | 20 AWG - 650 kcmil, solid or stranded. |
|
Insulation | XLPE; |
| Conductor size | Minimum average thickness in mils | Minimum thickness at any point in mils |
| 20-16 AWG | 41 | 37 |
| 15-10 AWG | 47 | 42 |
| 15-10 AWG | 47 | 42 |
| 9-2 AWG | 63 | 57 |
| 1-4/0 AWG | 78 | 70 |
| 250-500 kcmil | 94 | 85 |
| 550-650 kcmil | 109 | 98 min |
|
Standard | Appliance Wiring Material UL 758. |
|
Marking | General. |
|
Use | Internal wiring. |
|