APPLIANCE WIRING MATERIAL
Subj.758 Section 3 Page 3900 Issued:2011-11-04
Revised:New
Style 3900 Single Conductor with Extruded Insulation

Rating125 deg C, 7500 Vac, Horizontal Flame.
Conductor8 AWG - 600 kcmil, Solid or Stranded Round.
InsulationExtruded EPDM, 125 mils minimum average thickness, 112 mils minimum at any point.
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseInternal Wiring.

UL and the UL Logo are trademarks of UL LLC © 2024