Rating | 200 deg C, 600 Vac, Horizontal flame. |
|
Conductor | 50 AWG - 4/0 AWG, solid or stranded. |
|
Insulation | Extruded SR. |
| Conductor size (AWG) | Minimum average thickness (Mils) | Minimum thickness at any point (Mils) |
| 50 - 31 | 30 | 27 |
| 30 - 25 | 30 | 27 |
| 24 - 20 | 30 | 27 |
| 19 - 15 | 30 | 27 |
| 14 - 12 | 30 | 27 |
| 11 - 10 | 30 | 27 |
| 9 - 8 | 45 | 41 |
| 7 - 6 | 60 | 54 |
| 5 - 2 | 60 | 54 |
| 1 - 4/0 | 80 | 72 |
|
Standard | Appliance Wiring Material UL 758. |
|
Marking | General. |
|
Use | Internal Wiring. |
|