APPLIANCE WIRING MATERIAL
Subj.758 Section 4 Page 4179 Issued:1961-02-07
Revised:2012-07-15
Style 4179 Parallel Cable with Extruded Integral Insulation and Jacket

Rating90 deg C, 600 Vac, Horizontal Flame, Optional - Oil Resistant 60 deg C.
Conductor18 AWG - 16 AWG, Stranded Round, consisting of 30 AWG or smaller strands.
InsulationIntegral with Jacket. Extruded NBR/PVC, 60 mils minimum average, 54 mils minimum at any point.
AssemblyTwo conductor, same as type SP Cord, with a nominal 60 mils wall and the following (pin gauge) dimensions: Wall thickness: 0.058 in., Web thickness: 0.141 in., Wall after rip: 0.058 in.
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseInternal Wiring.