APPLIANCE WIRING MATERIAL
Subj.758 Section 4 Page 4244 Issued:1972-12-19
Revised:2011-11-09
Style 4244 Jacketed cable

Rating90 deg C, 600 Vac, FT2 flame, 60 deg C oil jacket.
Conductor18 AWG - 10 AWG solid or stranded round, tinned or bare copper.
InsulationEP, 31 mils min average, 28 mils minimum at any point. 10 AWG, 0.047 in. min. average, 0.043 in. min. at any point, and 18 AWG, 0.031 in. min. average, 0.028 in. min. at any point.
AssemblyTen conductors, same as type SO. 3-10 AWG and 7-18 AWG twisted together with jute filler and 7 in. maximum lay, 10 mils rubber filled tape or paper tape separator. Optional Nylon covering (4 mils) on insulated conductors.
JacketCP, 78 mils min average, 70 mils minimum at any point.
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseSuitable for use only in the wiring of x-ray machines.