APPLIANCE WIRING MATERIAL
Subj.758 Section 4 Page 4252 Issued:1974-03-18
Revised:2012-02-22
Style 4252 Multiple-conductor cable using non-integral jacket

Rating60 deg C, 300 Vac, FT2.
Conductor24 AWG - 18 AWG, solid or stranded, tinned soft cadmium copper strands or in accordance with the Standard. For stranded conductors, each strand shall be 36 AWG.
InsulationExtruded SBR/NR, 15 mils minimum average thickness, 13 mils minimum thickness at any point
AssemblyTwo to fourteen conductors, same as for type SVO. Maximum lay of conductors in any layer not more than 15 times outer diameter of that layer. Cable shall be coiled.
ShieldOptional.
JacketExtruded NBR/PVC, 45 mils minimum average thickness, 41 mils minimum thickness at any point.
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseInternal wiring of electronic equipment, (such as X-Ray equipment and business machines.