Rating | 105 deg C, voltage not specified, Cable flame. |
|
Conductor | 30 AWG - 9 AWG solid or stranded. |
|
Insulation | Labeled or complying with manufacturer's AWM procedure, 5 mils min average. |
|
Assembly | Two or more individually insulated conductors or groups of insulated conductors cabled together. All conductors in any group twisted together. If more than one group is used, groups shall also be twisted together. The length of lay of the twisted conductors or groups is not specified. A barrier layer, if employed, may be a fibrous wrap serving, or braid; paper; nylon; oriented polyethylene terephthalate; or a thermoplastic-tape wrap. Such a barrier layer would serve to protect the cable during further processing, and would be applied immediately over the twisted assembly of individual conductors or groups of conductors. |
|
Shield | Optional. |
|
Jacket | CP |
| dia of cable under jacket |
| 0.425 inches or less | 45 mils min average | 36 mils min at any point |
| 0.426-0.700 dia | 60 avg | 48 min |
| 0.701-1.500 dia | 78 avg | 62 min |
| 1.501-2.500 dia | 109 avg | 88 min |
| 2.501 dia or larger | 140 avg | 112 min |
|
Standard | Appliance Wiring Material UL 758. |
|
Marking | General. |
|
Use | Internal Wiring or External Interconnection of Electronic Equipment. |
|