APPLIANCE WIRING MATERIAL
Subj.758 Section 4 Page 4280 Issued:1977-09-14
Revised:2019-11-07
Style 4280 Multiple-conductor cable using non-integral jacket.

Rating80 deg C, voltage not specified, Cable flame.
Conductor30 AWG - 9 AWG solid or stranded.
InsulationLabeled complying with manufacturer's AWM Procedure.
AssemblyTwo or more individually insulated conductors or groups of insulated conductors cabled together. All conductors in any group twisted together. If more than one group is used, groups shall also be twisted together. The length of lay of the twisted conductors or groups is not specified. A barrier layer, if employed, may be a fibrous wrap serving, or braid; paper; nylon; oriented polyethylene terephthalate; or a thermoplastic-tape wrap. Such barrier layer would serve to protect the cable during further processing, and would be applied immediately over the twisted assembly of individual conductors or groups of conductors.
ShieldOptional.
CoveringOptional. A nominal 15 mils PVC covering may be extruded over the conductor assembly.
BraidOptional.
JacketExtruded CP
dia of cable under jacket
0.425 inches or less45 mils minimum average thickness36 mils minimum thickness at any point
0.426-0.700 dia60 avg48 min
0.701-1.500 dia78 avg62 minimum
1.501-2.500 dia109 avg88 minimum
2.501 dia and larger140 avg112 minimum
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseInternal Wiring or External Interconnection of Electronic Equipment.