Rating | 80 deg C, voltage not specified, Cable flame. |
|
Conductor | 30 AWG - 9 AWG solid or stranded. |
|
Insulation | Labeled complying with manufacturer's AWM Procedure. |
|
Assembly | Two or more individually insulated conductors or groups of insulated conductors cabled together. All conductors in any group twisted together. If more than one group is used, groups shall also be twisted together. The length of lay of the twisted conductors or groups is not specified. A barrier layer, if employed, may be a fibrous wrap serving, or braid; paper; nylon; oriented polyethylene terephthalate; or a thermoplastic-tape wrap. Such barrier layer would serve to protect the cable during further processing, and would be applied immediately over the twisted assembly of individual conductors or groups of conductors. |
|
Shield | Optional. |
|
Covering | Optional. A nominal 15 mils PVC covering may be extruded over the conductor assembly. |
|
Braid | Optional. |
|
Jacket | Extruded CP |
| dia of cable under jacket |
| 0.425 inches or less | 45 mils minimum average thickness | 36 mils minimum thickness at any point |
| 0.426-0.700 dia | 60 avg | 48 min |
| 0.701-1.500 dia | 78 avg | 62 minimum |
| 1.501-2.500 dia | 109 avg | 88 minimum |
| 2.501 dia and larger | 140 avg | 112 minimum |
|
Standard | Appliance Wiring Material UL 758. |
|
Marking | General. |
|
Use | Internal Wiring or External Interconnection of Electronic Equipment. |
|