APPLIANCE WIRING MATERIAL
Subj.758 Section 4 Page 4281 Issued:1977-09-14
Revised:2012-02-22
Style 4281 Multiple-conductor cable using non-integral jacket

Rating60 deg C, Voltage not Specified
Conductor22 AWG stranded round
InsulationExtruded SR, 30 mils minimum average thickness, 27 mils minimum thickness at any point. Control conductor, Style 1213.
AssemblyOne high voltage conductor and two control conductors are twisted with fillers. Lay of conductors not specified. Two conductor assemblies laid parallel.
CoveringFiberglass or nylon braid applied over assembly.
JacketExtruded CP, 40 mils minimum average thickness, 32 mils minimum thickness at any point. See Facing Page for Compound.
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseDefibrillator electrode connections where the acceptability of the combination has been determined by Underwriters Laboratories Inc.