APPLIANCE WIRING MATERIAL
Subj.758 Section 4 Page 4332 Issued:1982-12-27
Revised:2013-02-08
Style 4332 Multiconductor cable with extruded non-integral jacket

Rating60 deg C, voltage not specified, Cable flame.
Conductor40 AWG minimum.
Insulated ConductorLabeled or complying with manufacturer's AWM Procedure.
AssemblyTwo or more individually insulated conductors or groups of insulated conductors cabled together. The length of lay of the twisted conductors or groups is not specified. Fillers may be used in a cable but are not required. A barrier layer, if employed, may be a fibrous wrap serving, or braid; paper; nylon; oriented polyethylene terephthalate; or thermoplastic-tape wrap. Such a barrier layer would serve to protect the cable during further processing and would be applied immediately over the twisted assembly of individual conductors or groups of conductors.
ShieldOptional.
JacketExtruded EVA.
Diameter of cable under jacketMinimum average thicknessMinimum thickness at any point
0.700 inches or less45 mils36 mils
0.701-1.000 inch60 mils48 mils
1.001-1.500 inch80 mils64 mils
1.501-2.500 inch110 mils88 mils
2.501 inch and larger140 mils112 mils
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseInternal wiring or external interconnection of electronic equipment.