APPLIANCE WIRING MATERIAL
Subj.758 Section 4 Page 4349 Issued:1984-05-18
Revised:2019-11-07
Style 4349 Multiple-conductor cable using non-integral jacket

Rating105 deg C, 30 Vac, Cable flame.
Conductor40 AWG min - Material not specified.
InsulationLabeled or complies with manufacturer's AWM Singles Procedure.
AssemblyTwo or more twisted singles or groups of twisted singles twisted together. Lay not specified. Barrier layer and/or fillers optional, manufacturer shall maintain a complete description of each assembly.
ShieldOptional.
JacketExtruded SR
dia of cable under jacket
0.425 or less in inches45 mils min average36 mils minimum at any point
0.426-0.700 dia60 avg48 min
0.701-1.500 dia80 avg64 min
1.501-2.500 dia110 avg88 min
2.501 dia and larger140 avg112 min
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseAs internal wiring or external interconnection in Class 2 Circuits of electronics equipment. (such as electronic computers and electric business machines.)