| Rating | 60, 75, 90 deg C, 600 Vac, FT-2 Flame, 60 deg C Oil (for Jakcet). |
|
| Conductor | 18 AWG - 2 AWG, Solid or Stranded Round. |
|
| Insulation | Extruded EP or Extruded SBR/NR or Extruded Neoprene or Extruded CP or Extruded Thermoset CPE or Extruded NBR/PVC, Same as for Type SO except as described below. |
| Conductor AWG Size | mils minimum average | mils minimum at any point |
| 18-16 | 20 | 18 |
| 14-10 | 30 | 27 |
| 8-2 | 45 | 40 |
|
| Covering | Each insulated conductor shall have a 4 mil minimum at any point extruded Nylon covering. |
|
| Assembly | Same as for Type SO Cord. |
|
| Jacket | Extruded EPDM or Extruded Neoprene or Extruded CP or Extruded Thermoset CPE or Extruded NBR/PVR or Extruded SBR/NR, same as for Type SO Cord except as descibed below. |
| Diameter of cable under jacket in inches | mils minimum average | mils minimum at any point |
| 0.425 or less | 45 | 36 |
| 0.426-0.700 | 60 | 48 |
| 0.701-1.500 | 80 | 64 |
| 1.501-2.500 | 110 | 88 |
|
| Standard | Appliance Wiring Material UL 758. |
|
| Marking | General. |
|
| Use | Internal Wiring or External Interconnection. |
|