APPLIANCE WIRING MATERIAL
Subj.758 Section 4 Page 4372 Issued:1987-08-17
Revised:2012-04-02
Style 4372 Multiple-Conductor Cable Using Extruded Non-Integral Jacke

Rating105 deg C, 600 Vac, FT2 flame, Oil Resistant 60 deg C.
Conductor24 AWG - 4/0 AWG solid or stranded round, tinned or bare.
InsulationExtruded EP, Same as for Type SO Cord.
AWG Conductor SizeMinimum average thickness (mils)Minimum thickness at any point (mils)
24-163027
14-104540
8-26054
1-4/08072
AssemblySame as type SO Cord.
ShieldOptional
JacketExtruded EPDM - Same as for type SO Cord except
Diameter of core assembly under jacket (inches)Minimum average thickness (mils)Minimum thickness at any point (mils)
0.425 inches or less4536
0.426-0.7006048
0.701-1.5008064
1.501-2.50011088
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseInternal Wiring or external interconnection.